The cold shrink termination and joints are available for indoor & outdoor applications for single core and 3-core cables up to 36kV. They are manufactured from high quality liquid silicone rubber, which has high-quality electrical insulation, excellent tracking resistance as well as high elasticity.

Technical Performance

Items

8.7/15KV

12/24KV

18/36KV

Indoor Termination

Ac withstand voltage

rated

39KV, 5 min no flashover, no strike

81KV, 5 min no flashover, no strike

117KV, 5 min no flashover, no strike

Partial discharge test

13KV<5pc

31KV<10pc

45KV<10pc

Cyclic lad test

3 cycles under 90-100 ℃,23KV

3 cycles under 90-100 ℃,45KV

3 cycles under 90-100 ℃65KV

Impulses voltage test

95KV no flashover, no strike

170KV no flashover, no strike

200KV no flashover, no strike

15min, 50HZ Voltage

with standing test

23KV, 15min no flashover, no strike

45KV, 15min no flashover, no strike

65KV, 15min no flashover, no strike

Humidity test

No any flashover, tracking, erosion or mechanical damage occur at 300h, 11KV

No any flashover, tracking, erosion or mechanical damage occur at 300h,21KV

No any flashover, tracking, erosion or mechanical damage occur at 300h,32.5KV

Outdoor Termination

Ac withstand voltage

rated

39KV, 5 min          no flashover, no strike

81KV, 5 min          no flashover, no strike

117KV, 5 min          no flashover, no strike

Partial discharge test

13KV<5pc

31KV<10pc

45KV<10pc

Cyclic lad test

3 cycles under 90-100 ℃,23KV

3 cycles under 90-100 ℃,45KV

3 cycles under 90-100 ℃65KV

Impulses voltage test

95KV no flashover, no strike

170KV no flashover, no strike

200KV no flashover, no strike

15min, 50HZ Voltage

with standing test

23KV, 15min no flashover, no strike

45KV, 15min no flashover, no strike

65KV, 15min no flashover, no strike

Salt fog test

No any flashover, tracking, erosion or mechanical damage occur at 1000h, 11KV

No any flashover, tracking, erosion or mechanical damage occur at 1000h,21KV

No any flashover, tracking, erosion or mechanical damage occur at 1000h,32.5KV

Straight Joint

Ac withstand voltage

rated

39KV, 5 min          no flashover, no strike

81KV, 5 min          no flashover, no strike

117KV, 5 min          no flashover, no strike

Partial discharge test

15KV<10pc

31KV<10pc

45KV<10pc

Cyclic lad test

3 cycles under 90-100 ℃,23KV

3 cycles under 90-100 ℃,45KV

3 cycles under 90-100 ℃65KV

Impulses voltage test

95KV no flashover, no strike

170KV no flashover, no strike

200KV no flashover, no strike

15min, 50HZ Voltage

with standing test

23KV, 15min no flashover, no strike

45KV, 15min no flashover, no strike

65KV, 15min no flashover, no strike

Items

Requirements for Termination Kits for 8.7/15 KV Power Cable

(As per Specification P-184: 86, IEC 60502-4 & IEEE Std. 48)

Indoor Termination

Partial discharge test 13kv<5pc
Power frequency voltage 1Min( dry) withstand test No breakdown or flashover at 50KV
Power frequency voltage 6hrs(dry) withstand test No breakdown or flashover at 35Kv
Lightning impulse voltage withstand test at 110 KV on both polarities (+ve & – ve) No breakdown or flashover during 10 applications at 110Kv
DC withstand(dry) test for 15 min. No breakdown or flashover at 75Kv DC
Radio influence voltage(RIV) test RIV should not exceed 50uv when the samples is energized at 10Kv
Thermal short Circuit test The specified current should flow for 2s through the termination (02-applications). The terminations shall not have any damage.
Humidity test No any flashover, tracking, erosion or mechanical damage occur at 100h, 10.1KV
Cyclic Aging Test As per Specification

Outdoor Termination

Partial discharge test 13kv<5pc
Power frequency voltage 1Min( dry) withstand test No breakdown or flashover at 50KV
Power frequency voltage 10sec( wet) withstand test No breakdown or flashover at 45KV for 10s
Power frequency voltage 6hrs(dry) withstand test No breakdown or flashover at 35Kv
Lightning impulse voltage withstand test at 110Kv on both polarities (+ve & – ve) No breakdown or flashover during 10 applications at 110Kv
DC withstand(dry) test for 15 min. No breakdown or flashover at 75Kv DC
Radio influence voltage(RIV) test RIV should not exceed 50uv when the samples is energized at 10Kv
Thermal short Circuit test The specified current should flow for 2s through the termination (02-applications). The terminations shall not have any damage.
Tracking resistance test The leakage current through of the surface of the terminations should not exceed 500mA during 101 operation of rain ON/OFF (10 Second ON & 20 Second OFF)
Salt fog test No visible tracking or damage at 10.1Kv for 1 hour
Cyclic Aging Test As per Specification

Straight Joints

Partial discharge test 15kv<10pc
AC withstand (dry) test at 39.5Kv for 5 min. No breakdown or flashover at 39.5KV
AC withstand (dry) test at21.75Kv for 15 min. No breakdown or flashover at 21.75 KV
Lightning impulse voltage withstand test at 95 KV No breakdown or flashover during 10 applications for both +ve & -ve polarities at 95Kv
DC withstand(dry) test at 34.8 KV for 15 min. No breakdown or flashover at 34.8Kv DC
Thermal short Circuit test (conductor) The specified current should flow for 2s through the joint (Cable Conductor) (02-applications). The joint shall not have any sign of damage.
Thermal short Circuit test (screen) The specified current should flow for 2s through the joint (Cable Screen) (02-applications). The joint shall not have any sign of damage.

Specification

1kV  cold shrinkable cable accessories

Type Size Range(mm2)
1KV XLPE 4 cores Termination 1KVCDT-4/0 10~16
1KVCDT-4/1 25~50
1KVCDT-4/2 70~120
1KVCDT-4/3 150~240
1KVCDT-4/4 300-400

15Kv cold shrinkable XLPE cable accessories

Type Size Range(mm2)
8.7/15KV XLPE  cable(1 core) Indoor termination
8.7/15KVCDLN-1/1 25-50
8.7/15KVCDLN-1/2 70-120
8.7/15KVCDLN-1/3 150-240
8.7/15KVCDLN-1/4 300
8.7/15KVCDLN-1/5 400
8.7/15KVCDLN-1/6 500
8.7/15KVCDLN-1/7 630
8.7/15KVCDLN-1/8 800
8.7/15KV XLPE cable(1core) Outdoor termination 8.7/15KVCDLW-1/1 25-50
8.7/15KVCDLW-1/2 70-120
8.7/15KVCDLW-1/3 150-240
8.7/15KVCDLW-1/4 300
8.7/15KVCDLW-1/5 400
8.7/15KVCDLW-1/6 500
8.7/15KVCDLW-1/7 630
8.7/15KVCDLW-1/8 800
8.7/15KV XLPE cable(1core) Straight joint 8.7/15KVCDLJ-1/1 25-50
8.7/15KVCDLJ-1/2 70-120
8.7/15KVCDLJ-1/3 150-240
8.7/15KVCDLJ-1/4 300
8.7/15KVCDLJ-1/5 400-500
8.7/15KVCDLJ-1/6 630-800
8.7/15KV XLPE cable(3 core) Indoor termination 8.7/15KVCDLN-3/1 25-50
8.7/15KVCDLN-3/2 70-120
8.7/15KVCDLN-3/3 150-240
8.7/15KVCDLN-3/4 300-400
8.7/15KVCDLN-3/5 500-630
8.7/15KVRSWY-3/5 500-630
8.7/15KV XLPE cable(3 core)   Outdoor termination 8.7/15KVCDLW-3/1 25-50
8.7/15KVCDLW-3/2 70-120
8.7/15KVCDLW-3/3 150-240
8.7/15KVCDLW-3/4 300-400
8.7/15KVCDLW-3/5 500-630
8.7/15KV XLPE cable(3 core) Straight joint 8.7/15KVCDLJ-3/1 25-50
8.7/15KVCDLJ-3/2 70-120
8.7/15KVCDLJ-3/3 150-240
8.7/15KVCDLJ-3/4 300

24Kv cold shrinkable XLPE power cable accessories

Type Size Range(mm2)
12/24KV XLPE cable(1 core) Indoor termination 12/24KVCDLN-1/1 25-50
12/24KVCDLN-1/2 70-120
12/24KVCDLN-1/3 150-240
12/24KVCDLN-1/4 300- -400
12/24KV XLPE cable(1core) Outdoor termination 12/24KVCDLW-1/1 25-50
12/24KVCDLW-1/2 70-120
12/24KVCDLW-1/3 150-240
12/24KVCDLW-1/4 300–400
12/24KV XLPE cable(1core) Straight joint 12/24KVCDLJ-1/1 25-50
12/24KVCDLJ-1/2 70-120
12/24KVCDLJ-1/3 150-240
12/24KVCDLJ-1/4 300–400
12/24KV XLPE cable(3 core) Indoor termination 12/24KVCDLN-3/1 25-50
12/24KVCDLN-3/2 70-120
12/24KVCDLN-3/3 150-240
12/24KVCDLN-3/4 300-400
12/24KV XLPE cable(3 core)   Outdoor termination 12/24KVCDLW-3/1 25-50
12/24KVCDLW-3/2 70-120
12/24KVCDLW-3/3 150-240
12/24KVCDLW-3/4 300-400
12/24KV XLPE cable(3 core) Straight joint 12/24KVCDLJ-3/1 25-50
12/24KVCDLJ-3/2 70-120
12/24KVCDLJ-3/3 150-240
12/24KVCDLJ-3/4 300–400

36KV cold shrinkable XLPE cable accessories

Type Size Range(mm2)
36Kv indoor termination for 1-core 35KVCDLN-1/1 50-120
35kVCDLN-1/2 150-240
35kVCDLN-1/3 300-630
36Kv outdoor termination for 1-core 35KVCDLW-1/1 50-120
35kVCDLW-1/2 150-240
35kVCDLW-1/3 300-630
36Kv straight joint for  1-core 35KVCDLJ-1/1 50-120
35kVCDLJ-1/2 150-240
35kVCDLJ-1/3 300-630
36Kv indoor termination for 3-core 35KVCDLN-3/1 50-95
35kVCDLN-3/2 120-185
35kVCDLN-3/3 240-400
36Kv outdoor termination for 3-core 35KVCDLW-3/1 50-95
35kVCDLW-3/2 120-185
35kVCDLW-3/3 240-400
36Kv straight joint for  3-core 35KVCDLJ-3/1 50-95
35kVCDLJ-3/2 120-185
35kVCDLJ-3/3 240-400